Over-temperature water can cause serious burns to employees using safety shower, face wash, and eye wash equipment. Modulating thermostatic scald protection valves can be installed on the highest point of the emergency equipment to sense the ambient or fluid temperature.
These valves are designed to open and drain off when an overheated water temperature is sensed. Typical set points of 105°F to 115°F control water temperatures to safe levels. Refer to our model HAT/SP valve for product information.